The RA1216 family combines analog input, analog output, and digital I/O in an intelligent remote data acquisition pod. The base unit communicates with a host computer through an optically isolated, half-duplex RS-485 interface. An on-board microcontroller and local memory support data collection close to sensors and equipment.
Analog Inputs and Signal Conditioning
The 12-bit successive-approximation converter accepts sixteen single-ended or eight differential inputs. Programmable gain and offset allow channels to be configured for different signal spans. The voltage-input model offers spans from 25 mV to 5 V, with bipolar operation available through the offset circuitry. Inputs include protection to 200 VDC.
Choose RA1216 for voltage inputs, RA1216T/C for up to seven thermocouples with cold-junction sensing, RA1216R for up to eight three-wire RTDs, RA1216I for up to eight 4-20 mA transmitter inputs, or RA1216B/C for eight quarter-bridge strain-gage completion circuits. Thermocouple break-detection resistors can be specified when ordering.
Voltage and Current Outputs
Three independent 12-bit D/A channels provide voltage and current outputs simultaneously. Each voltage output is programmable for 0-5 V or 0-10 V. The 4-20 mA outputs require a user-supplied compliance voltage of 5.5-30 V.
Digital Control and Remote Installation
Seven digital lines are individually programmable as inputs or open-collector outputs. Outputs support user-supplied voltages up to 50 VDC and sink up to 350 mA per line, subject to a combined 650 mA limit. Inductive-kick suppression is provided. A watchdog timer resets the controller following processor or supply faults.
The NEMA 4 enclosure includes internal screw terminals and a cable gland for field wiring. Separate supplies power the local circuitry and isolated serial interface to maintain isolation. The U-, WM-, E-, and S-prefix packages provide USB, wireless, Ethernet, and RS-232 host connectivity respectively.
Customized Analog I/O (MCOTS Options)
ACCES specializes in modified-COTS analog I/O. We can customize voltage ranges, sampling rates, filtering, isolation, gain stages, calibration profiles, firmware behavior, connector styles, and environmental ruggedness. If your analog requirements are unique, we excel at delivering tailored MCOTS analog hardware quickly and cost-effectively.